PowerMan Online Double Conversion UPS 10000VA, 380/400V, 40 x 12V/7Ah Batteries, LCD Display, Zero transfer time, Lightning and Surge protection built in ( Compatible with most brands of generator), Pure Sine Wave, 3 Phase

R60,291.33 (Incl. VAT)

Description

PM33-HF010S

10KVA On-Line UPS, 3-phase input and output with internal battery pack

Rating: 10 KVA / 9 KW

Battery Pack: 40 x 12V7Ah Sealed Batteries

USB Comms: Standard

SNMP Card: Optional โ€“ includes software

Wave Form: Pure Sine Wave

Recharge: 80% after 9 hours

Run Times @ given load: 25% for 36 Minutes, 50% for 18 Minutes, 75% for 9 Minutes

UPS Dimensions (W) x (L) x (H) and Weight: 250mm x 840mm x 715mm @ 51.5Kg

Battery Pack Dimensions (W) x (L) x (H) and Weight: 950mm x 880mm x 1190mm @ 140Kg

 

Model No.

PM33-HF010S

PM33-HF020S

Capacity VA (Watts)

10 000 (10 000) 20 000 (18 000)

Input Voltage

3-Phase + Neutral + Earth 380V / 400V / 415 VAC line to line

Input Voltage Range

304 to 478 V line to line at full load

Input Frequency Range

40Hz to 70Hz

Total Harmonic Distortion (THDi)

< 4% < 3%

Input Power Factor

< 0.99

Output Voltage On Inverter (adjustable)

380V / 400V / 415 VAC line to line 230V AC + 3% line to neutral

Voltage Regulation

+ 1.5%

Frequency on Inverter

50 Hz Crystal Controlled (+ 0.01%)

Inverter Wave Form

Sine

Total Harmonic Distortion (THDu)

< 1% For Linear Loads ; < 5.5% Non-Linear Loads

Transfer Time

Zero

Efficiency At Full Load

> 95%

Overload Capability

110% for 60 minutes, 150% For 1 minute, then by-pass

Battery Voltage

+ 240VDC

Batteries

Internal battery pack, 40 x 12V Internal battery pack, 40 x 12V 7Ah Sealed Lead Acid 12Ah Sealed Lead Acid

Re-Charge to 90 %

+ 8 Hours

Backup Time With 50% Load (50% Load)

18 Minutes 20 Minutes

Backup Time With 75% Load (75% Load)

9 Minutes 10 Minutes

Ambient Operation

3000M Max Elevation, -10 to 40 C, 0 to 90% Humidity

Audible Noise At 1 M

< 60% Load 52 dbA / > 60% Load 56 dbA

Short Circuit Protection

Yes

Low Battery Shut down

Yes

Controls

Mains Fail Alarm (Slow intermittent beep), Low Battery Alarm (Continuous beep), Mains on indicator, Charging indicator, By-Pass Indicator, LCD Display (Full UPS Status reporting), Diagnostic software via USB port (SNMP and dry contact optional)

UPS Dimensions (w x d x h) mm & Weight

250mm x 840mm x 715mm 350mm x 730mm x 1335mm @ 135Kg @ 200Kg

 

Please refer to our Privacy Policy