PowerMan Online Double Conversion UPS 10000VA, 380/400V, 40 x 12V/7Ah Batteries, LCD Display, Zero transfer time, Lightning and Surge protection built in ( Compatible with most brands of generator), Pure Sine Wave, 3 Phase

R60,291.33 (Incl. VAT)

Description

PM33-HF010S

10KVA On-Line UPS, 3-phase input and output with internal battery pack

Rating: 10 KVA / 9 KW

Battery Pack: 40 x 12V7Ah Sealed Batteries

USB Comms: Standard

SNMP Card: Optional – includes software

Wave Form: Pure Sine Wave

Recharge: 80% after 9 hours

Run Times @ given load: 25% for 36 Minutes, 50% for 18 Minutes, 75% for 9 Minutes

UPS Dimensions (W) x (L) x (H) and Weight: 250mm x 840mm x 715mm @ 51.5Kg

Battery Pack Dimensions (W) x (L) x (H) and Weight: 950mm x 880mm x 1190mm @ 140Kg

 

Model No.

PM33-HF010S

PM33-HF020S

Capacity VA (Watts)

10 000 (10 000) 20 000 (18 000)

Input Voltage

3-Phase + Neutral + Earth 380V / 400V / 415 VAC line to line

Input Voltage Range

304 to 478 V line to line at full load

Input Frequency Range

40Hz to 70Hz

Total Harmonic Distortion (THDi)

< 4% < 3%

Input Power Factor

< 0.99

Output Voltage On Inverter (adjustable)

380V / 400V / 415 VAC line to line 230V AC + 3% line to neutral

Voltage Regulation

+ 1.5%

Frequency on Inverter

50 Hz Crystal Controlled (+ 0.01%)

Inverter Wave Form

Sine

Total Harmonic Distortion (THDu)

< 1% For Linear Loads ; < 5.5% Non-Linear Loads

Transfer Time

Zero

Efficiency At Full Load

> 95%

Overload Capability

110% for 60 minutes, 150% For 1 minute, then by-pass

Battery Voltage

+ 240VDC

Batteries

Internal battery pack, 40 x 12V Internal battery pack, 40 x 12V 7Ah Sealed Lead Acid 12Ah Sealed Lead Acid

Re-Charge to 90 %

+ 8 Hours

Backup Time With 50% Load (50% Load)

18 Minutes 20 Minutes

Backup Time With 75% Load (75% Load)

9 Minutes 10 Minutes

Ambient Operation

3000M Max Elevation, -10 to 40 C, 0 to 90% Humidity

Audible Noise At 1 M

< 60% Load 52 dbA / > 60% Load 56 dbA

Short Circuit Protection

Yes

Low Battery Shut down

Yes

Controls

Mains Fail Alarm (Slow intermittent beep), Low Battery Alarm (Continuous beep), Mains on indicator, Charging indicator, By-Pass Indicator, LCD Display (Full UPS Status reporting), Diagnostic software via USB port (SNMP and dry contact optional)

UPS Dimensions (w x d x h) mm & Weight

250mm x 840mm x 715mm 350mm x 730mm x 1335mm @ 135Kg @ 200Kg

 

Please refer to our Privacy Policy
We will send an SMS to this number as soon as your quote is ready.
Provide an additional landline or mobile number to contact you.
Left Menu Icon
Cart Menu Button Image0Right Menu Icon
Your Cart