Specification Details
Cells Per Unit 6
Voltage Per Unit 12
Capacity 100Ah @ 10hr-rate to 1.8V per cell @25°C (77°F)
Weight Approx. 29 kg(64.68 lbs)
Maximum Discharge Current 1200A (5sec)
Internal Resistance Approx. 5.5 mΩ
Operating Temperature Range Discharge: -15°C~50°C ( 5°F~122°F)
Charge: -15°C~40°C ( 5°F~104°F)
Storage: -15°C~40°C ( 5°F~104°F)
Nominal Operating Temperature Range 25°C±3°C (77°F±5°F)
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging Current Limit 30A
Equalisation and Cycle Service 14.4 to 14.8 VDC/unit Average at 25°C (77°F)
Self Discharge Batteries can be stored for more than 6 months at 25°C (77°F). Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal Thread lead alloy recessed terminal to accept M6 bolt
Container Material ABS(UL 94-HB) & Flammability resistance of (UL 94-V0) available upon request