Description
GKPS-22
PERKINS 20KVA SINGLE PHASE (GKPS-22)
- Maximum 22kVA standby power at 230v @50Hz 1500rpm
- Ideal for home and small business applications
- Silent canopy which can stand outside with lockable doors
- Automatic changeover (ATS), maintenance free batteries and trickle charger included
- Long range diesel tank allows for longer run times (180l)
- Powerful four cylinder 1500rpm water cooled 404A-22G1 Perkins diesel engine
- H-specification insulation, brushless alternator with AVR provides stable output
- Easy to use digital controller with auto and manual start options
- High temperature and low oil, water and fuel protection to protect against engine damage
- Peace of mind of earlier of one year/1000 hour warranty vs traditional 3000rpm sets at six months/500 hours
- Improved fuel consumption and better reliability/longer lifespan than 3000rpm units
Engine
- Perkins diesel engine
- Four cylinder, water cooled
- Electronic governor control system
- 12v DC starter and charge alternator
- Replaceable fuel filter, oil filter and dry element air filter
- Cooling radiator and fan
- Exhaust silencer
- Maintenance free battery including rack and cables
Alternator
- Brushless, single bearing system, four poles
- Insulation class H with circuit breaker protection
- Standard degree of protection IP22
- Self-exciting and self-regulating
- Screen protected and drip proof
- Automatic voltage regulator
Chassis
- The complete generator set is mounted as a whole on a heavy duty, fabricated, steel base frame
- Steel chassis and antivibration pads
- Base frame design incorporates an integral fuel tank
- The generator can be lifted or carefully pushed/pulled by the base frame
- Dial type fuel gauge on the fuel tank
Canopy
- Ventilation parts are designed with modular principles
- Weather resistant and lined with sound reducing foam
- All metal canopy parts are painted by powder paint
- Panel window
- Lockable doors on each side
- Easy maintenance and operation
- Easy lifting and moving
- Insulated engine exhaust system
- Exterior emergency stop push button
- Sound attenuated
Control system
Control supervision and protection panel is mounted on the genset base frame. The control panel is equipped as follows:
Auto mains failure control panel
- Control with Stromer automatic transfer switch
- HGM6120N Smartgen electronic controller
- Emergency stop push button
- Static battery charger
- Four-pole electrically and mechanically interlocked ATS
Generating set control module HGM6120N Smartgen features
- This module is used to monitor a mains supply and automatically start a standby generating set
- Microprocessor-based design
- Monitors engine performance and AC power output
- LCD and LED alarm notification
- Front panel configuration of timers and alarm trip points
- Provides signal to change over switch panel
- Shutdown alarms
- STOP/RESET-MANUAL-AUTO-START
- Operation indicators accessed be the LCD display scroll push button
Metering via LCD display
- Mains volts (L-L/L-N)
- Generator amps (L1, L2, L3)
- Generator frequency; generator (cos)
- Engine hours run; plant battery (volts)
- Engine oil pressure (psi and bar)
- Engine speed (rpm)
- Engine temperature (ËšC)
Automatic shutdown and fault conditions
- Under/over speed; fail to start
- High engine temperature; fail to stop
- Low oil pressure; charge fail
- Under/over generator volts
- Under/over generator frequency; emergency stop
- Start failure
- Under/over mains voltage
- Charge failure
- Low diesel level; low oil pressure
*All ratings are quoted at maximum ratings at sea level and derating will be applicable for altitude and power factor.