Description
SUN-50K-P3
Deye Hybrid inverter, 3- phase, 50Kw, 160-800V, 4 MPPT, 50000W
- 100% unbalanced output;each phase
- AC couple to retrofit existing solar system
- *Max. 10 pcs parallel for on-grid and off-grid operation
- Support multiple batteries parallel
- Max. charging/discharging current of 100A
- High voltage battery, higher efficiency
- 6 time periods for battery charging/discharging
- Support storing energy from diesel generator
Specifications:
Category | Specification |
---|---|
Model | SUN-50K-P3 |
Battery Input Data | |
Battery Type | Lithium-ion |
Battery Voltage Range (V) | 160~800 |
Max. Charging Current (A) | 50+50 |
Max. Discharging Current (A) | 50+50 |
Number of Battery input | 2 |
Charging Strategy for Li-Ion Battery | Self-adaption to BMS |
PV String Input Data | |
Max. DC Input Power (W) | 65000 |
Max. DC Input Voltage (V) | 1000 |
Start-up Voltage (V) | 180 |
MPPT Range (V) | 150-850 |
Full Load DC Voltage Range (V) | 450-850 |
Rated DC Input Voltage (V) | 600 |
PV Input Current (A) | 36+36+36+36 |
Max. PV ISC (A) | 55+55+55+55 |
No. of MPP Trackers | 4 |
No. of Strings per MPP Tracker | 2+2+2+2 |
AC Output Data | |
Rated AC Output and UPS Power (W) | 50000 |
Max. AC Output Power (W) | 55000 |
AC Output Rated Current (A) | 75.8/72.5 |
Max. AC Output Current (A) | 83.4/79.7 |
Max. AC Current (A) | 83.3 |
Max. Continuous AC Passthrough (A) | 200 |
Peak Power (off grid) | 1.5 times of rated power, 10 S |
Power Factor Adjustment Range | 0.8 leading to 0.8 lagging |
Rated Input/Output Voltage/Range(V) | 220/380, 230/400 0.85Un-1.1Un |
Rated Input/Output Grid Frequency/Range | 50Hz/45Hz-55Hz 60Hz/55Hz-65Hz |
Grid Connection Form | 3L+N+PE |
Total Harmonics Current Distortion (THDi) | <3% (of nominal power) |
DC Current Injection | <0.5% ln |
Efficiency | |
Max. Efficiency | 97.60% |
Euro Efficiency | 97.00% |
MPPT Efficiency | 99.90% |
Protection | |
Integrated | Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge Protection, Arc Fault Circuit Interruption (AFCI optional) |
Over Voltage Category | DC Type II / AC Type Ⅲ |
Certifications and Standards | |
Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
General Data | |
Operating Temperature Range (℃) | -40 to +60℃, >45℃ Derating |
Cooling | Smart cooling |
Noise (dB) | ≤65 dB |
Communication with BMS | CAN |
Weight (kg) | 80 |
Cabinet Size (WxHxD mm) | 527×894×294 (Excluding Connectors and Brackets) |
Protection Degree | IP65 |
Installation Style | Wall-mounted |
Warranty | 5 Years/10 Years (the Warranty Period Depends on the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy) |
Datasheet: