Mecer 3000VA 2U on-line 

    • ONLINE UPS
    • True double-conversion
    • Microprocessor control optimizes reliability
    • Input power factor correction 0.99
    • Output power factor 0.8
    • Wide input voltage (110 V–300 V)
    • Converter mode available
    • ECO mode for energy saving
    • Generator compatible
    • Adjustable battery numbers only available for 6K and up models
    • Smart SNMP works well with either USB or RS-232 together
    • Emergency power off function only available for 6K and up models

Specifications:

SKU ME-3000-WPTU
WEIGHT 27.6000
PHYSICAL DIMENSIONS 421 x 190 x 318 (mm)
CAPACITY 3000 VA / 2400 W
VOLTAGE RANGE LOW LINE TRANSFER 160VAC/140VAC/120VAC/110VAC±5% ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
VOLTAGE RANGE LOW LINE COMEBACK 168VAC/148VAC/128VAC/118VAC ± 5 % ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
VOLTAGE RANGE HIGH LINE TRANSFER 300 VAC ± 5 %
VOLTAGE RANGE HIGH LINE COMEBACK 290 VAC ± 5 %
FREQUENCY RANGE 40Hz ~ 70 Hz
PHASE Single phase with ground
POWER FACTOR ≧ 0.99 @ nominal voltage (input voltage)
OUTPUT VOLTAGE 200/208/220/230/240VAC
AC VOLTAGE REGULATION (BATT. MODE) ±1% (Batt. Mode)
FREQUENCY RANGE (SYNCHRONIZED RANGE) 47 ~ 53 Hz or 57 ~ 63 Hz
FREQUENCY RANGE (BATT. MODE) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
OVERLOAD Sounding twice every second
CURRENT CREST RATIO 3:1
HARMONIC DISTORTION ≦ 3 % THD (linear load) ≦ 6 % THD (non-linear load)
WAVEFORM (BATT. MODE) Pure Sinewave
AC TO DC Zero
INVERTER TO BYPASS 4 ms (Typical)
AC MODE 90%
BATTERY MODE 88%
BATTERY TYPE 12 V / 9 AH
NUMBERS 6
RECHARGE TIME 4 hours recover to 90% capacity (Typical)
CHARGING CURRENT 1.0 A (max.)
CHARGING VOLTAGE 82.1 VDC ±1%
BATTERY TYPE & NUMBERS No
CHARGING CURRENT No
CHARGING VOLTAGE No
HUMIDITY 20-90 % RH @ 0- 40°C (non-condensing)
NOISE LEVEL Less than 50dBA @ 1 Meter
OPTIONAL USB/RS-232 PORT Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
OPTIONAL SNMP Power management from SNMP manager and web browser